Fire Dampers Inspection |
|
Manual: Life Safety and Interim Life Safety Management Manual (Ver 4) Department: ENGINEERING External Reference: (JCAHO EC.5.10, EC.5.40)
MCN’s customizable template, Fire Dampers Inspection, is taken from our Life Safety and Interim Life Safety Management Manual. MCN Healthcare’s proven policy and procedure templates, competencies and compliance tools have assisted more than 20,000 health care organizations worldwide meet their regulatory compliance goals. MCN’s templates save you time, money and resources, rather than developing healthcare policy and procedure manuals from scratch. Here is some sample content from Fire Dampers Inspection:
| | POLICY:
Fire dampers will be inspected annually in accordance with the following procedures. Newly installed equipment is to receive full scale operating test. The air-handling and smoke management system must include all areas of the building. All fire and smoke dampers shall be operated fusible links removed where applicable at least every four 4 years to insure they fully close.
PROCEDURE:
Note:
Determine that access door is reasonably air tight and latches properly.
If damper is closed, check for ruptured fusible links, broken attachment or hinges, damage, corrosion, etc.
Remove... |
| Second excerpt: |
| | ...fusible link and check for proper rating.
Determine that damper is self-closing and properly latches. Adjust if necessary.
Lubricate friction points and exercise damper to ensure complete freedom of movement.
Each year, in areas of vibration, install new fusible links of proper rating and tensile strength.
Reinstall fusible link locations where vibration is not a problem.
Close access door and check for wind noise.
Note:
SUBJECT:
FIRE DAMPERS INSPECTION
REFERENCE #1046
PAGE: ... |
|